Communications infrastructure runs continuously. Telecommunications carriers, broadcasters, streaming platforms, internet service providers and network operations centres cannot absorb unplanned downtime, not for seconds, let alone minutes. A power problem at a transmission site, broadcast facility or network node means dropped calls, interrupted live broadcasts, corrupted data streams and SLA breaches.
Most of those problems are predictable. This article sets out seven things that go wrong with power in communications and broadcast sites, and how each one is solved. For the full list of NPS solutions for the sector, see the communications industry page.
1. The Mains Dips or Drops and the Broadcast Stops
What goes wrong: Radio transmission equipment, studio systems and streaming servers are sensitive to power fluctuations and cannot tolerate unplanned outages. For a broadcaster, downtime is not just an IT problem. Dead air means lost audience.
The fix: An online double-conversion UPS runs the load through its inverter all the time, so there is zero transfer time and the equipment never sees a break in supply. This is the type NPS specifies for broadcast and telecommunications facilities that need clean, stable power and seamless switchover.
Hope Media, a Sydney broadcaster, is a recent example. NPS supplied an Eaton 93T 15kVA online double-conversion UPS, commissioned in August 2026, to protect its broadcast transmission and studio infrastructure. The unit sits between the mains and the equipment, filters power quality events before they reach it, and gives the team runtime to move to generator power or shut down safely if an outage runs long. Not sure which type suits your site? Read Online vs Line-Interactive UPS.
2. Servicing or Growth Forces the Load Offline
What goes wrong: Live broadcast and telecommunications infrastructure cannot be taken offline for planned or unplanned maintenance without a major operational impact. Network capacity also grows over time, and a UPS that cannot grow with it becomes a replacement project.
The fix: Design for maintenance and growth from the start. The Eaton 93T at Hope Media has an external maintenance bypass, so the unit can be serviced without interrupting the protected load. Redundant configurations, such as N+1, share the load across the remaining modules if one goes offline. Modular UPS architectures from Eaton, APC by Schneider Electric and Socomec let capacity be added without disruption to live systems, and the Socomec Modulys GP range scales from 25 to 600kVA. See Navigating UPS Redundancy and UPS preventative maintenance, which NPS backs with a 24/7 service hotline and rapid breakdown response.
3. Dirty Power Corrupts the Signal
What goes wrong: For sensitive signal and audio equipment, power quality matters as much as power continuity. Harmonic distortion and voltage fluctuations can corrupt signals and introduce interference into audio and video streams.
The fix: Start by measuring. A power quality audit logs supply voltage, sags, swells, transients and harmonics over a representative period, typically around a week, and gives you a written report on what was found. An online UPS then isolates the equipment from voltage fluctuations, frequency variations and harmonics. Read what a power quality audit finds.
4. Lightning Hits the Tower and the Damage Arrives Down the Cable
What goes wrong: Transmission towers and antenna infrastructure are highly exposed to lightning and electrical surge. Lightning can damage a site in two ways: a direct strike, and a surge that travels in through power, data and telephone lines. A surge lasting microseconds can destroy communications equipment.
The fix: Each risk needs its own protection, and a UPS is not rated to absorb a lightning-induced transient. A lightning protection system gives a strike a controlled path to earth. A cascade of surge protective devices (Type 1 at the main switchboard, Type 2 at distribution boards and Type 3 at the point of use) deals with what travels along the cables. Data and telephone lines need their own protectors, and a lightning warning system gives early notice of an approaching storm. NPS starts with a site survey, not a catalogue. See Lightning Protection Systems and Surge Protection and lightning and surge protection.
5. A Remote Site Loses the Mains and Nobody Is There
What goes wrong: Many communications sites are in remote areas with limited access to utility power and grid infrastructure. Edge and distributed sites often have no generator and no on-site staff, so an extended outage has nothing to fall back on.
The fix: A right-sized UPS carries the load instantly when the supply fails, and battery storage and generator integration sustain it. A generator is a companion to a UPS, not a replacement: the UPS covers the switchover and the generator carries the load for as long as it has fuel. Pre-integrated edge computing systems combine power protection, compact cooling, secure enclosures and remote monitoring for sites that were never built to house IT. NPS also supplies generators, and its field technicians can reach remote and regional sites across Australia.
6. The Equipment Room Overheats
What goes wrong: High-density communications equipment generates significant heat, and so does the UPS protecting it. Get cooling wrong and you risk thermal shutdowns, shortened hardware life and unplanned downtime.
The fix: Precision cooling that runs continuously, controls humidity as well as temperature, and is sized to the heat load of the equipment in the room. A regular monthly health check covers refrigerant levels, filters and airflow. Read How to Cool a Small Server Room or Comms Room, and the NPS precision cooling guide for larger rooms.
7. Nobody Notices the Problem Until It Is an Outage
What goes wrong: At unmanned and distributed sites, a failing battery, a rising temperature or a repeated mains event goes unseen until it causes downtime. Batteries are the part of a UPS most likely to fail, and the part least likely to warn you first.
The fix: Remote monitoring. SNMP network cards put each UPS on the network so it can raise alerts and trigger a graceful shutdown, environmental sensors watch temperature, humidity, water, smoke and doors, and management software brings every unit into one view, giving early warning of battery decline, load changes, temperature rises and mains events. Pair it with regular battery testing and know the signs your batteries need replacing. See power management and monitoring and battery maintenance and replacement.
How NPS Works Through a Communications Project
NPS handles the whole job, from turnkey power solutions (site assessment, load analysis, UPS system design and project management) through installation and commissioning, including battery and load tests, to maintenance and battery replacement. NPS is vendor agnostic, specifying Eaton, APC by Schneider Electric, Socomec or Vertiv based on the site, with factory-trained technicians for all major brands and 24/7 emergency support for live environments. For over 30 years NPS has protected communications infrastructure across Australia and New Zealand, with offices in Sydney, Melbourne, Brisbane and Perth.
A Quick Check for Your Own Site
- Does a short mains dip or outage reach your live equipment?
- Can a UPS be serviced without taking the load offline?
- Do you know what your supply quality looks like?
- Are power, data and telephone lines protected against surge, and the tower or antenna against lightning?
- How long can a remote site run on battery and generator, and who knows when it is happening?
- Is the equipment room cooled for the heat load it carries, with alarms if cooling fails?
Frequently Asked Questions About Communications Site Power
What type of UPS suits a broadcast or telecommunications facility?
An online double-conversion UPS. It provides clean, stable power output and seamless switchover, with zero transfer time to battery.
Why does power quality matter for broadcast equipment?
Harmonic distortion and voltage fluctuations can corrupt signals and introduce interference into audio and video streams, so clean, stable power output is essential as well as continuity of supply.
How do you protect a transmission tower from lightning?
A lightning protection system gives a strike a controlled path to earth, and surge protective devices at the main switchboard, distribution boards and point of use protect equipment from surges that travel along power, data and telephone lines. NPS designs this from a site survey.
What keeps a remote communications site running during a long outage?
A UPS carries the load instantly when the supply fails, and battery storage and generator integration sustain it for as long as the outage lasts. Remote monitoring shows head office what is happening at an unmanned site.
Can a UPS be serviced without turning off a live broadcast?
Some UPS systems have a maintenance bypass, which lets the unit be serviced without interrupting the protected load. The Eaton 93T installed for Hope Media has an external maintenance bypass, and redundant or modular configurations add further protection.
How do I monitor power at an unmanned site?
SNMP network cards put each UPS on the network, environmental sensors track temperature, humidity, water, smoke and doors, and management software brings every unit into one view with alerting. This gives early warning of battery decline, load changes, temperature rises and mains events.
Does NPS support communications sites outside the capital cities?
Yes. NPS has field technicians across all Australian states and can access remote and regional sites, with offices in Sydney, Melbourne, Brisbane and Perth and 24/7 emergency support for live environments.
Talk to NPS About Your Communications Site
If you recognise one of these problems on your site, NPS can assess it and recommend the fix. See the communications industry page, or contact the team to talk through your site.